The ISOWIND panel range is an insulated panel which can be used for temperature control and food & hygiene safe applications within an internal temperature range between +40°C and -40°C. Applications include food processing, chill/cold store and deep freeze, and clean room environments. |
Insulation Panel - Heat Transmission |
Thermal Conductivity (λ) 0.023 W/mk |
Heat Transmission : W/sq. m |
||||
Panel Thickness(mm) |
60 |
100 |
130 |
150 |
Thermal Transmittance W/sq.m K |
0.25 |
0.20 |
0.16 |
0.13 |
Temp. Difference |
||||
10°C |
2.5 |
2.00 |
1.60 |
1.30 |
15°C |
3.75 |
3.00 |
2.40 |
1.95 |
20°C |
5.00 |
4.00 |
3.20 |
2.60 |
25°C |
6.25 |
5.00 |
4.00 |
3.25 |
30°C |
7.50 |
6.00 |
4.80 |
3.90 |
35°C |
8.75 |
7.00 |
5.60 |
4.55 |
40°C |
10.00 |
8.00 |
6.40 |
5.20 |
45°C |
11.25 |
9.00 |
7.20 |
5.85 |
50°C |
12.50 |
10.00 |
8.00 |
6.50 |
The recommended minimum insulation value for coldstores is 10W/m2 heat gain.
To calculate the above use : D = λ x #t /Q
Where:
D = thickness of insulation (mm)
λ = lambda value of insulation (W/mK)
#t = temperature difference between internal and external face.
Q = heat flow = 10(W/sq. m)