Welcome to ISOWIND




The ISOWIND panel range is an insulated panel which can be used for temperature control and food & hygiene safe applications within an internal temperature range between +40°C and -40°C. Applications include food processing, chill/cold store and deep freeze, and clean room environments.


Insulation Panel - Heat Transmission

Thermal Conductivity (λ) 0.023 W/mk

Heat Transmission : W/sq. m

Panel Thickness(mm)

60

100

130

150

Thermal Transmittance W/sq.m K

0.25

0.20

0.16

0.13

Temp. Difference

10°C

2.5

2.00

1.60

1.30

15°C

3.75

3.00

2.40

1.95

20°C

5.00

4.00

3.20

2.60

25°C

6.25

5.00

4.00

3.25

30°C

7.50

6.00

4.80

3.90

35°C

8.75

7.00

5.60

4.55

40°C

10.00

8.00

6.40

5.20

45°C

11.25

9.00

7.20

5.85

50°C

12.50

10.00

8.00

6.50

The recommended minimum insulation value for coldstores is 10W/m2 heat gain.
To calculate the above use : D = λ x #t /Q

Where:
D = thickness of insulation (mm)
λ = lambda value of insulation (W/mK)
#t = temperature difference between internal and external face.
Q = heat flow = 10(W/sq. m)